about us
News Center
Your current location:Home - About us - News center
DeviceNet runs on a single cable that carries 24 V DC power, a common return, a twisted pair for CAN_H and CAN_L, and a drain wire for shielding. ODVA defines this as a trunk-and-drop architecture: the trunk runs the length of the line and is terminated at both ends, while each device hangs off it on a short drop. A 5-pin splitter is the physical junction where that division happens, and every other layout question — where it goes, how many devices it serves, how long a branch can run — follows from it.
The M12 5-pin pinout used on DeviceNet assigns Pin 1 to drain and shield, Pin 2 to V+ (24 V DC), Pin 3 to V− (common), Pin 4 to CAN_H, and Pin 5 to CAN_L. Two pins deliver power, two carry the differential data pair, and one carries the shield. That mix is why a DeviceNet node can be fed from the same cable that carries its data, and why a splitter has to pass all five signals through rather than just the data pair. The body is A-coded, the coding shared across industrial sensor and bus connectors, and the thread-locking coupling holds the junction sealed and vibration-resistant once it is tightened.
The trunk is the backbone: it runs between the two end nodes, ends in termination resistors (121 Ω on DeviceNet), and carries power for the whole segment. Drops are the short spurs that leave the trunk at a tap and reach a device or a small cluster. DeviceNet limits both the length of a single drop and the total of all drops, and those limits tighten as the data rate rises: at 500 kbit/s a single drop is about 6 m and the cumulative budget is roughly 39 m, while at 125 kbit/s the cumulative budget grows to around 156 m. A splitter's three outputs are all drops, which is why placing one near the devices it feeds keeps a segment inside budget and stringing long outputs across a cabinet does the opposite.